Altronix - AL600ULM - Power Supply with Fire Alarm Disconnect
Ideal for a multitude of purposes, including CCTV, Fire Alarm and POIP. A leading global provider of power and transmission technologies for professional security system applications, Altronix develops innovative solutions that integrate disparate infrastructure and maximize overall performance and efficiency.
Altronix Power Supplies are ideal for a multitude of purposes, including:
- General Use
- CCTV
- Fire Alarm
- POIP
Input:
- Input 115VAC, 60Hz, 3.5A
- Input fuse rated @ 3.5A/250V.
- Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C. supervised trigger input and polarity reversal trigger input.
Output:
- 12VDC or 24VDC selectable outputs
- 6A supply current.
- Five (5) PTC protected Class 2 Rated power limited outputs, rated @ 2A (auto-resettable).
- Output relay energizes when unit is triggered (form "C" contact rated 1A @ 28VDC).
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection
Battery Backup:
- Built-in charger for sealed lead acid or gel type batteries
- Automatic switch over to stand-by battery when AC fails.
Supervision:
- AC fail supervision (form "C" contacts).
- Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
- Low battery supervision (form "C" contact).
- Battery presence supervision (form "C" contact).
- Power fail supervision relay (form "C" contacts)
Visual Indicators:
- AC input and DC output LED indicators (power supply board)
- Red LEDs indicate condition of power outputs (multi-output board)
- Power and input trigger LEDs (multi-output board)
Temperature:
- Operating 0° C to 49° C (32° F to 120° F)
- Storage: - 20° C to 70ºC ( - 4° F to 158° F)
- Relative Humidity 85% +/- 5%
- BTU/Hr (approx.):
12VDC: 37 BTU/Hr
24VDC: 74 BTU/Hr - System AC input VA requirement:
166.75VA.(AL600ULM)
402.5VA(AL600ULMR)
Enclosure:
- Wall mount enclosure for indoor use.
- Accommodates up to two (2) 12VDC/12AH Batteries.
- Dimensions 13"W x 13.5"H x 3.25"D (330 mm W x 343 mm H x 83 mm D).
- 1/2" and 3/4" combination knockouts